Branch circuit breakers and wire sizes can be set automatically based upon the connected load of the branch circuit.

If you open a current project, all of the breaker sizes will be locked to match your current breaker sizes. Locking the breaker sizes ensures drastic changes are not made to the breaker sizes in your current project when loading the add-in.

On new projects, the breaker sizes will be set to Size Automatically. They will be sized based upon 125% of the connected load of the branch circuit.

To override the sizes, use the Circuit Edit command. This command allows you to set specific breaker and wire sizes. This functionality is useful when you need to adjust a breaker size for a piece of equipment or the wire size to account for voltage drop. You can also use this command on current projects to change the breaker size back to Size Automatically.

The branch circuit breaker size uses the Rating value of the circuit. It should be displayed automatically for you in your panel schedule.

The branch circuit wire sizes use custom shared parameter values. You have to manually modify your panel schedule to display these values. See the Modifying Panel Schedules section for more information about how to make these values appear.