Feeder Shared Parameters

The shared parameters added to distribution equipment related to the feeder to the distribution equipment.

Numeric Parameters

Parameter types in this section are set to number unless otherwise noted.

DMEN_Feeder_ConductorWireArea: The area of the conductor wire as an area parameter. The area is for a single conductor wire. It does not account for parallel runs or the number of poles.

DMEN_Feeder_ConduitArea: The area of the conduit as an area parameter.

DMEN_Feeder_ConduitFill: The conduit fill as a percentage.

DMEN_Feeder_EffectiveZPer1000ft: The effective Z per 1,000' for the feeder. Used to calculate voltage drop.

DMEN_Feeder_FrameSize: The frame size of the upstream OCP for the distribution equipment as a current parameter.

DMEN_Feeder_GroundWireArea: The area of the ground wire as an area parameter.

DMEN_Feeder_Length: The length of the feeder as a length parameter.

DMEN_Feeder_NeutralWireArea: The area of the neutral wire as an area parameter.

DMEN_Feeder_NeutralWireCount: The number of neutral wires.

DMEN_Feeder_ParallelRuns: The number of parallel runs.

DMEN_Feeder_RPer1000ft: The resistance per 1,000' for the feeder.

DMEN_Feeder_TripSize: The trip size of the upstream OCP for the distribution equipment as a current parameter.

DMEN_Feeder_WireAmpacity: The ampacity of the feeder as a current parameter.

DMEN_Feeder_XPer1000ft: The reactance per 1,000' for the feeder.

DMEN_Feeder_ZPer1000ft: The impedance per 1,000' for the feeder.

DMEN_Feeder2_ConductorWireArea: The area of the conductor wire of the second feeder as an area parameter. The area is for a single conductor wire. It does not account for parallel runs or the number of poles.

DMEN_Feeder2_ConduitArea: The area of the conduit of the second feeder as an area parameter.

DMEN_Feeder2_ConduitFill: The conduit fill of the second feeder as a percentage.

DMEN_Feeder_EffectiveZPer1000ft: The effective Z per 1,000' for the second feeder. Used to calculate voltage drop.

DMEN_Feeder2_FrameSize: The frame size of the upstream OCP of the second feeder for the distribution equipment as a current parameter.

DMEN_Feeder2_GroundWireArea: The area of the ground wire of the second feeder as an area parameter.

DMEN_Feeder2_Length: The length of the feeder of the second feeder as a length parameter.

DMEN_Feeder2_NeutralWireArea: The area of the neutral wire of the second feeder as an area parameter.

DMEN_Feeder2_NeutralWireCount: The number of neutral wires of the second feeder.

DMEN_Feeder2_ParallelRuns: The number of parallel runs of the second feeder.

DMEN_Feeder2_RPer1000ft: The resistance per 1,000' for the second feeder.

DMEN_Feeder2_TripSize: The trip size of the upstream OCP for the distribution equipment of the second feeder as a current parameter.

DMEN_Feeder2_WireAmpacity: The ampacity of the second feeder as a current parameter.

DMEN_Feeder2_XPer1000ft: The reactance per 1,000' for the second feeder.

DMEN_Feeder2_ZPer1000ft: The impedance per 1,000' for the second feeder.

Text Parameters

Parameter types in this section are set to text.

DMET_Feeder_ConductorWireArea: The area of the conductor wire. The area is for a single conductor wire. It does not account for parallel runs or the number of poles. If there are two feeders, both conductor sizes are shown, separated by a slash. The default feeder schedule includes this parameter as a hidden column and sorts the schedule using it.

DMET_Feeder_ConductorWireSize: The number of parallel runs and the size of the conductor wires. Displayed in the default fault current schedule. If there are two feeders, both feeder sizes are shown, separated by a slash.

DMET_Feeder_ConductorWireSizeOnly: The size of the conductor wires. If there are two feeders, both feeder sizes are shown, separated by a slash.

DMET_Feeder_ConduitFill: The conduit fill as a percentage. If there are two feeders, both conduit fills are shown, separated by a slash.

DMET_Feeder_ConduitSize: The size of the conduit. If there are two feeders, both conduit sizes are shown, separated by a slash.

DMET_Feeder_Display: A Yes or No value that indicates whether the feeder should be displayed in the feeder schedule. The default feeder schedule includes this parameter as a hidden column. Any distribution equipment with the value set to No is not included in the schedule. Pieces of electrical equipment with their Part Type set to Equipment Switch are automatically set to No so they are not displayed in the schedule.

DMET_Feeder_EffectiveZPer1000ft: The effective Z per 1,000' for the feeder. Used to calculate voltage drop. If there are two feeders, both values are shown, separated by a slash.

DMET_Feeder_FeederID: The feeder ID on the one-line diagram of the first feeder.

DMET_Feeder_FrameSize: The frame size of the upstream OCP of the first feeder for the distribution equipment.

DMET_Feeder_GroundWireSize: The size of the ground wire. If there are two feeders, both ground wire sizes are shown, separated by a slash.

DMET_Feeder_IGConductor: A Yes or No value that indicates whether the first feeder includes an IG conductor.

DMET_Feeder_Length_ft: The length of the feeder in feet. If there are two feeders, both lengths are shown, separated by a slash. Displayed in the default fault current schedule.

DMET_Feeder_Length_m: The length of the feeder in meters. If there are two feeders, both lengths are shown, separated by a slash.

DMET_Feeder_NeutralWireSize: The size of the neutral wire. If there are two feeders, both neutral wire sizes are shown, separated by a slash.

DMET_Feeder_ParallelRuns: The number of parallel runs of the first feeder.

DMET_Feeder_RPer1000ft: The resistance of the feeder per 1,000'. If there are two feeders, both resistances are shown, separated by a slash.

DMET_Feeder_Trip_Poles: The trip size and number of poles of the upstream OCP of the first feeder for the distribution equipment. The trip and poles are separated by a slash, for example, 100/3.

DMET_Feeder_TripSize: The trip size of the upstream OCP of the first feeder for the distribution equipment.

DMET_Feeder_WireAmpacity: The ampacity of the feeder wire of the first feeder.

DMET_Feeder_WireCallout: The callout of the first feeder. The callout lists the conduit size and all of the wire sizes, separated by a comma and a space.

DMET_Feeder_WireCalloutCompact: The callout of the first feeder. The callout lists the conduit size and all of the wire sizes, separated by a comma.

DMET_Feeder_XPer1000ft: The reactance of the feeder per 1,000'. If there are two feeders, both reactances are shown, separated by a slash.

DMET_Feeder_ZPer1000ft: The impedance of the feeder per 1,000'. If there are two feeders, both impedances are shown, separated by a slash.

DMET_Feeder1_ConductorWireArea: The area of the conductor wire of the first feeder. The area is for a single conductor wire. It does not account for parallel runs or the number of poles.

DMET_Feeder1_ConductorWireSize: The number of parallel runs and the size of the conductor wires of the first feeder.

DMET_Feeder1_ConductorWireSizeOnly: The size of the conductor wires of the first feeder.

DMET_Feeder1_ConduitSize: The size of the conduit of the first feeder.

DMET_Feeder1_EffectiveZPer1000ft: The effective Z per 1,000' of the first feeder. Used to calculate voltage drop.

DMET_Feeder1_GroundWireSize: The size of the ground wire of the first feeder.

DMET_Feeder1_Length_ft: The length in feet of the first feeder.

DMET_Feeder1_Length_m: The length in meters of the first feeder.

DMET_Feeder1_NeutralWireSize: The size of the neutral wire of the first feeder.

DMET_Feeder1_RPer1000ft: The resistance per 1,000' of the first feeder.

DMET_Feeder1_XPer1000ft: The reactance per 1,000' of the first feeder.

DMET_Feeder1_ZPer1000ft: The impedance per 1,000' of the first feeder.

DMET_Feeder2_ConductorWireArea: The area of the conductor wire of the second feeder. The area is for a single conductor wire. It does not account for parallel runs or the number of poles.

DMET_Feeder2_ConductorWireSize: The number of parallel runs and the size of the conductor wires of the second feeder.

DMET_Feeder2_ConductorWireSizeOnly: The size of the conductor wires of the second feeder.

DMET_Feeder2_ConduitFill: The conduit fill of the second feeder as a percentage.

DMET_Feeder2_ConduitSize: The size of the conduit of the second feeder.

DMET_Feeder2_Display: A Yes or No value that indicates whether the feeder should be displayed in the feeder schedule. Pieces of electrical equipment with their Part Type set to Equipment Switch are automatically set to No so they are not displayed in the schedule.

DMET_Feeder2_FeederID: The feeder ID on the one-line diagram of the second feeder.

DMET_Feeder2_FrameSize: The frame size of the upstream OCP of the second feeder for the distribution equipment.

DMET_Feeder2_EffectiveZPer1000ft: The effective Z per 1,000' of the second feeder. Used to calculate voltage drop.

DMET_Feeder2_GroundWireSize: The size of the ground wire of the second feeder.

DMET_Feeder2_IGConductor: A Yes or No value that indicates whether the second feeder includes an IG conductor.

DMET_Feeder2_Length_ft: The length in feet of the second feeder.

DMET_Feeder2_Length_m: The length in meters of the second feeder.

DMET_Feeder2_NeutralWireSize: The size of the neutral wire of the second feeder.

DMET_Feeder2_ParallelRuns: The number of parallel runs of the second feeder.

DMET_Feeder2_RPer1000ft: The resistance per 1,000' of the second feeder.

DMET_Feeder2_TripSize: The trip size of the upstream OCP of the second feeder for the distribution equipment.

DMET_Feeder2_WireAmpacity: The ampacity of the second feeder.

DMET_Feeder2_WireCallout: The callout of the second feeder. The callout lists the conduit size and all of the wire sizes, separated by a comma and a space.

DMET_Feeder2_WireCalloutCompact: The callout of the second feeder. The callout lists the conduit size and all of the wire sizes, separated by a comma.

DMET_Feeder2_XPer1000ft: The reactance per 1,000' of the second feeder.

DMET_Feeder2_ZPer1000ft: The impedance per 1,000' of the second feeder.

Yes/No Parameters

Parameter types in this section are set to yes/no.

DMEB_Feeder_NeutralDouble: Whether the neutral wire of the first feeder is set to double the phase wire.

DMEB_Feeder2_NeutralDouble: Whether the neutral wire of the second feeder is set to double the phase wire.


Page url: http://www.designmaster.biz/docs/elecrt/2.0/index.html?feeder_shared_parameters.htm
©2013-2021 Design Master Software, Inc