8.2.4 Update

Released October 29, 2012

The new options for equipment are described below. A new field, FLA / BCSC, was added. New choices for Breaker Size and Wire Size were added. These new features were added to better support NEC 430 and NEC 440.

FLA / BCSC: Full load current or branch-circuit selection current. It is used to size the breaker according to NEC 430.52 and 440.22, depending upon the Breaker Size selection. It is also used in one of the Wire Size options. (This field is new in this release.)

MCA: Minimum circuit amps. This is used to size the conductors. It is not used in any of the calculations for the breaker size. (This field previously existed.)

MOCP: Maximum overcurrent protection. Use when sizing motor-compressor breakers, but not when sizing motor breakers. (This field previously existed.)

Breaker Size: How the breaker for the equipment is sized. (This field previously existed but now has more choices.)

Wire Size: How the conductors for the equipment are sized. (This field previously existed but now has more choices.)