2006 International Mechanical Code

This section describes the ventilation schedule that is printed when the Ventilation Calculation Method field in the Project Info command is set to 2006 International Mechanical Code.

Ventilation Schedule

The Ventilation Schedule table contains sections for the zones in the project. If the whole building is selected to be printed in the Zone or Room to Print list, then every zone will be listed. If specific zones are selected, then only the selected zones are displayed and no sections are displayed.

The labels in parentheses for the columns are the names of the variables used in the 2006 IMC calculations.

The room with the highest Uncorrected OSA, Fraction is highlighted in bold.

Each zone is displayed as a separate section in the table. A header with the name of the zone is displayed at the top of each section.

Load Calculations--Print Load Calculations.Print Ventilation Schedule.2006 IMC

Location: The zone and the rooms in the zone. Rooms are indented below the zone.

Room Type: Only used for rooms. Set using the Room Type field in the Edit Rooms command.

For zones, the cell is blank.

Ventilation Requirements: Set using the Cooling 1, Cooling 2, Heating 1 and Heating 2 fields in the Ventilation section of the Edit Rooms or Room Project Schedule command.

Area: The area of the room. Set based upon the room boundary inserted on the drawing.

People: The total number of people in the room or zone. If Allow Fractional People is unchecked in the Project Info command, this value will be rounded to the nearest whole person.

For rooms, set using the SF / Person or People fields in the People section of the Edit Rooms or Room Project Schedule command

For zones, set using the SF / Person or People field in the Zone List command. If a value is not specified in these fields, the number of people is the sum of the people in the rooms in the zone.

Supply CFM (Vst): The supply airflow required to condition the room or zone. This value is the same as the Required Supply CFM column in the Supply Air Requirements table. See the Print Supply Air Requirements section for more information.

Uncorrected OSA, CFM (Von): The ventilation airflow for the room or zone based upon the settings in the rooms and room schedule.

For rooms, set using the Cooling 1 and Cooling 2 fields in the Ventilation section of the Edit Rooms or Room Project Schedule command.

For zones, the ventilation airflow is the sum of the airflows of the rooms in the zone.

Uncorrected OSA, Fraction (X): The fraction of supply air that is outside air. Equal to Uncorrected OSA, CFM divided by Supply CFM. The room with the highest Uncorrected OSA, Fraction is highlighted in bold.

Critical Space OSA, Fraction (Z): The largest Uncorrected OSA, Fraction for the zone. This value is only listed on the zone row.

Corrected OSA, CFM (Vot): The ventilation airflow volume calculated by the 2006 IMC calculation. This value is used to determine the ventilation load for the zone.

Corrected OSA, Fraction (Y): The fraction of supply air that is outside air. Equal to Corrected OSA, CFM divided by Supply CFM.