Zone List |
Up Previous Next |
To create or modify a zone, go to Ribbon: DM HVAC->Building Definition-> Pulldown Menu: DM HVAC->Building Definition->Zones->Zone List Zones Dialog Box See the Common Schedule Dialog Box Features section for more information about how this dialog box works. This section describes the Rename, Find, Previous, Next, New, Copy, Save, and Delete buttons. Zone Above: The zone that is above this zone in the zone hierarchy.
System Type: The type of system that is modeled by the zone.
Room Supply Airflow Basis: How the room supply airflow is calculated.
Fixed Supply Airflow: The total airflow to be supplied to the zone when Room Supply Airflow Basis is set to Prorate using fixed supply airflow. This field is disabled if Room Supply Airflow Basis is set to Use calculated room loads. Room Ventilation Airflow Basis: How the room ventilation airflow is calculated.
Fixed Ventilation Airflow: The total ventilation for the zone when Room Ventilation Airflow Basis is set to Use fixed ventilation airflow. This field is disabled if Room Ventilation Airflow Basis is set to Use room settings. Indoor Air Defaults The Indoor Air Defaults section sets the default temperature and humidity values for rooms in the zone. These values can be overridden for specific room types or individual rooms. If Zone Above is set to <None>, these values must be entered manually. If Zone Above has a zone selected, these values are set based upon the above zone. Check the first box beside this section to specify a different Heating Temperature and/or Cooling Temperature for this zone. Check the second box beside this section to specify a different Relative Humidity for this zone. Heating Temperature: The goal temperature when heating rooms in the zone. Cooling Temperature: The goal temperature when cooling rooms in the zone. Relative Humidity (%): The goal relative humidity when cooling rooms in the zone. ASHRAE 62 The ASHRAE 62 section sets values that are used when performing the ASHRAE 62.1 zone ventilation calculation. If Zone Above is set to <None>, these values must be entered manually. If Zone Above has a zone selected, these values are set based upon the above zone. Check the box beside this section to specify different values for this zone. The descriptions for these values are based upon their definitions in ASHRAE 62.1-2004, Appendix A: Definitions. Show Definition: Press this button next to each value to display the ASHRAE 62.1 definition for the value. Ep: Primary air fraction to the zone. Set Ep to 1.0 for single-duct and single-zone systems. Er: In systems with secondary recirculation of return air, fraction of secondary recirculated air to the zone that is representative of average system return air rather than air directly recirculated from the zone. For plenum return systems with local secondary recirculation (e.g., fan-powered VAV with plenum return), set Er less than or equal to 1.0. For ducted return systems with local secondary recirculation (e.g., fan-powered VAV with ducted return), typically Er is equal 0.0. Ez: A measure of how effectively the zone air distribution uses its supply air to maintain acceptable air quality in the breathing zone.
Minimum Zd: The minimum discharge outdoor air fraction for the zone. The formal definition is Zd = Voz/Vdz. Voz is the zone outdoor airflow. Vdz is the zone discharge airflow. For non-VAV systems, this value should be set to 0. For VAV systems, Vdz is the minimum expected discharge airflow for design purposes. You must determine what the minimum discharge outdoor air fraction for the system will be. The minimum Zd that you specify implicitly defines the minimum Vdz for the zone. The People Diversity section sets whether the number of people in the zone is diversified compared to the number of people in the rooms in the zone. If the checkbox is unchecked, the number of people in the zone is the sum of the number of people in the rooms in the zone. If the checkbox is checked, the number of people in the zone is based upon the SF / Person or People setting. The people load in the zone will be adjusted accordingly. SF / Person: Select this option to set the number of people in the zone based upon the zone area. People: Select this option to set the total number of people in the zone. Plenum The Plenum section controls whether the zone has a plenum return. When a zone has a plenum return, some of the room loads are moved to the system load instead. These include the roof load, the portion of the wall load that is above the plenum, and a percentage of the lighting load. If Zone Above is set to <None>, these values can be entered manually. If Zone Above has a zone selected, these values are set based upon the above zone. Check the box beside this section to specify different values for this zone. Plenum Return: Whether the zone has a plenum return. Percentage of Lighting Load to Plenum: For zones with a plenum return, the percentage of the lighting load that is transferred to the plenum. The lighting load in the plenum is included in the system load but not the room load. Tempered Air The Tempered Air section controls whether the zone has tempered air and the settings of the tempered air if it does. If Zone Above is set to <None>, these values can be entered manually. If Zone Above has a zone selected, these values are set based upon the above zone. Check the box beside this section to specify different values for this zone. OSA is Tempered: Whether the outside air is tempered before it reaches the air handler. Tempered Low Temperature: If OSA is Tempered is checked, this temperature is used instead of the OSA Low Temperature Dry Bulb temperature when calculating heating loads. Tempered High Dry Bulb Temperature: If OSA is Tempered is checked, this temperature is used instead of the OSA High Dry temperature when calculating cooling loads. Tempered High Wet Bulb Temperature: Whether the web bulb temperature is tempered in addition to the dry bulb temperature. If this is checked, this temperature is used instead of the OSA High Wet temperature when calculating cooling loads.. AHU and Coil Settings The AHU and Coil Settings section controls values that are used in the supply air requirements calculations and the psychrometric calculations. If Zone Above is set to <None>, these values must be entered manually. If Zone Above has a zone selected, these values are set based upon the above zone. Check the box beside this section to specify different values for this zone. Heating Temperature Difference: The difference between the heating temperature in the room or zone and the temperature of the air at the supply diffusers. This temperature difference is used as an input in the heating supply air requirement calculations. Cooling Temperature: The temperature of the air at the supply diffusers. This temperature is used as the desired end condition for the psychrometric calculations and as an input in the cooling supply air requirements calculations. Coil Bypass Factor (%): The percentage of air that is not conditioned by the coil. Fan Position: Where the fan is positioned relative to the coil.
Fan Brake Horsepower: The horsepower of the fan brake. Motor Position: Where the motor is positioned relative to the ductwork.
Motor Efficiency (%): The efficiency of the motor. Higher valued result in lower temperature gains from the motor. Duct Settings The Duct Settings section controls values in the ductwork that are used in the psychrometric calculations. If Zone Above is set to <None>, these values must be entered manually. If Zone Above has a zone selected, these values are set based upon the above zone. Check the box beside this section to specify different values for this zone. Supply Duct Temperature Gain: The change in temperature of the air traveling through the supply ductwork. This temperature gain is often caused by ductwork in unconditioned spaces, typically outside. An increase in this value results in a lower coil dew point temperature. Supply Duct Air Leakage (%): The percentage of supply air that is leaked out of the ductwork. This air is leaked outside the building. Do not include air that is leaked out of the ductwork but remains inside the building. An increase in this value results in an increase in the mixed air volume. If the amount of air leaked exceeds the outside air volume, it will increase the volume of outside air required. Return Duct Temperature Gain: The change in temperature of the air traveling through the return ductwork. The temperature gain is often caused by ductwork in unconditioned spaces, typically outside. An increase in this value results in a higher mixed air temperature and a higher coil dew point temperature. Return Duct Air Leakage (%): The percentage of return air that is leaked out of the ductwork. This air is leaked outside the building. Do not include air that is leaked out of the ductwork but remains inside the building. An increase in this value results in an increase in the outside air volume. |
Page url:
http://www.designmaster.biz/docs/hvac/index.html?zone_list.htm
©2012-2023 Design Master Software, Inc |