Skip to main content

Shared Parameters

ElectroBIM adds shared parameters to distribution equipment and branch circuits in Revit. They can be used like any other shared parameters. Some of them are used in the default schedules created by the Schedules commands.

tip

See the Making Changes: Don't Modify the Shared Parameters and Panel Schedules sections for more information about using our shared parameters.

ElectroBIM shared parameters are all prefixed with DME:

  •  Text parameters begin with DMET. Their parameter Data Type ▾ is set to Text.

  •  Numeric parameters begin with DMEN. These parameters use appropriate units where possible; otherwise, their parameter Data Type ▾ is set to Number.

  •  Yes/no parameters begin with DMEB. Their parameter Data Type ▾ is set to Yes/No.

  •  Revit duplicate parameters begin with DMER. These parameters are used with single-line diagram graphics and will reflect the value of the corresponding Revit built-in parameter for the corresponding device in the model. These parameters are not meant to be used in schedules or in the model.
    For example, on a panel that has the Revit Panel Name parameter set to MDP-1, the corresponding single-line diagram graphic for the panel will display MDP-1 for the DMER_Panel_Name shared parameter.

Shared Parameter Files​

Shared parameter files that contain ElectroBIM shared parameters are located where ElectroBIM is installed. The default install location is
C:\Program Files\Design Master Software\Electrical RT.

The name of each file corresponds to its intended Revit version. For example, DesignMasterElectricalRT2024.txt should be used with Revit 2024.

Related Options

Output shared parameter values as uppercase: Sets whether shared parameter outputs are displayed only in uppercase letters.

Panel Shared Parameters​

The general shared parameters added to distribution equipment.

Numeric Parameters​

  •  DMEN_Panel_LineToLineVoltage The line-to-line voltage of the distribution equipment as an electrical potential parameter.

  •  DMEN_Panel_LineToNeutralVoltage The line-to-neutral voltage of the distribution equipment as an electrical potential parameter.

  •  DMEN_Panel_MainDisconnectFrameSize The frame size of the main disconnect as a current parameter.

  •  DMEN_Panel_MainDisconnectPoles The number of poles of the main disconnect as an integer parameter.

  •  DMEN_Panel_MainDisconnectTripSize The trip size of the main disconnect as a current parameter.

  •  DMEN_Panel_MainDisconnectType The type of main disconnect as an integer parameter.

    tip

    By default, this shared parameter is used by some single-line diagram graphic families to control the main disconnect graphic displayed on the bus bar.

    It can also be used in formulas to display different values based upon the main disconnect type. See the Main Disconnect Type Formula article in the knowledge base for more information.

    •  0 The main disconnect is main lugs only.
    •  1 The main disconnect is a main circuit breaker.
    •  2 The main disconnect is a fused switch.

Text Parameters​

  •  DMET_Panel_BusAmps The bus amps of the distribution equipment.

  •  DMET_Panel_Distribution_System The distribution system of the distribution equipment.

    tip

    The built-in Revit Distribution System property cannot be included in schedules. Use this parameter to include the value in a schedule.

  •  DMET_Panel_FedFrom The upstream device feeding the distribution equipment.

  •  DMET_Panel_FedFrom2 The upstream device connected to the second feeder of the distribution equipment.

  •  DMET_Panel_FedFromCircuit The circuit on the upstream device to which the distribution equipment is connected.

  •  DMET_Panel_FedFromCircuit2 The circuit on the upstream device to which the second feeder of distribution equipment is connected.

  •  DMET_Panel_LineToLineVoltage The line-to-line voltage of the distribution equipment.

  •  DMET_Panel_LineToNeutralVoltage The line-to-neutral voltage of the distribution equipment.

  •  DMET_Panel_Lugs The type of lugs specified for the distribution equipment.

  •  DMET_Panel_MainDisconnect The main disconnect type, trip, and frame size, together in a single shared parameter. The numbers listed below are example values.

    •  MLO The main disconnect is main lugs only.
    •  MCB 100A The main disconnect is a main circuit breaker with the same size frame and trip.
    •  MCB 60AT, 100AF The main disconnect is a main circuit breaker with different frame and trip sizes. The trip size is labeled AT (for "amps trip") and the frame size is labeled AF (for "amps frame").
    •  FS 100A The main disconnect is a fused switch with the same size frame and trip.
    •  FS 60AT, 100AF The main disconnect is a fused switch with different frame and trip sizes. The trip size is labeled AT (for "amps trip") and the frame size is labeled AF (for "amps frame").
  •  DMET_Panel_MainDisconnectFrameSize The frame size of the main disconnect.

  •  DMET_Panel_MainDisconnectPoles The number of poles of the main disconnect.

  •  DMET_Panel_MainDisconnectTripSize The trip size of the main disconnect.

  •  DMET_Panel_MainDisconnectType The type of main disconnect.

    •  MLO The main disconnect is main lugs only.
    •  MCB The main disconnect is a main circuit breaker.
    •  FS The main disconnect is a fused switch.
  •  DMET_PanelTree_Label The name of the distribution equipment, indented based upon its position in the model. The indent begins with a period because Revit removes any leading spaces in the value.

  •  DMET_PanelTree_SortOrder A number representing the position of the distribution equipment in the panel tree. When the schedule is sorted by this parameter, the DMET_PanelTree_Label column will display the panel tree in the correct order.

  •  DMET_Panel_UpstreamDescription The description for the distribution equipment as it appears in the circuit description of the upstream panel schedule.

  •  DMET_Panel_UpstreamDescription2 The description for the second feeder of the distribution equipment as it appears in the circuit description of the upstream panel schedule.

Transformer Shared Parameters​

The shared parameters added to transformers.

Numeric Parameters​

  •  DMEN_Transformer_PrimaryCurrent_Calculated The total calculated demand current of the transformer at the primary voltage.

  •  DMEN_Transformer_PrimaryCurrent_Connected The total connected current of the transformer at the primary voltage.

  •  DMEN_Transformer_VA The size of the transformer as a power parameter.

  •  DMEN_Transformer_XRRatio The X/R ratio of the transformer.

  •  DMEN_Transformer_Z The impedance of the transformer.

Text Parameters​

  •  DMET_Transformer_KFactor The K-factor rating of the transformer.

  •  DMET_Transformer_kVA The size of the transformer in kVA.

  •  DMET_Transformer_Secondary_Distribution_System The secondary distribution system of the distribution equipment.

    tip

    The built-in Revit Secondary Distribution System property cannot be included in schedules. Use this parameter to include the value in a schedule.

  •  DMET_Transformer_XRRatio The X/R ratio of the transformer.

  •  DMET_Transformer_Z The impedance of the transformer.

Feeder Shared Parameters​

The shared parameters added to distribution equipment that are related to the feeder to the distribution equipment.

Numeric Parameters​

  •  DMEN_Feeder_ConductorWireArea The area of the conductor wire as an area parameter. The area is for a single conductor wire. It does not account for parallel runs or the number of poles.

  •  DMEN_Feeder_ConduitArea The area of the conduit as an area parameter.

  •  DMEN_Feeder_ConduitFill The conduit fill as a percentage.

  •  DMEN_Feeder_EffectiveZPer1000ft The effective Z per 1,000' for the feeder. Used to calculate voltage drop.

  •  DMEN_Feeder_FrameSize The frame size of the upstream OCP for the distribution equipment as a current parameter.

  •  DMEN_Feeder_GroundWireArea The area of the ground wire as an area parameter.

  •  DMEN_Feeder_Length The length of the feeder as a length parameter.

  •  DMEN_Feeder_NeutralWireArea The area of the neutral wire as an area parameter.

  •  DMEN_Feeder_NeutralWireCount The number of neutral wires.

  •  DMEN_Feeder_ParallelRuns The number of parallel runs.

  •  DMEN_Feeder_RPer1000ft The resistance per 1,000' for the feeder.

  •  DMEN_Feeder_TripSize The trip size of the upstream OCP for the distribution equipment as a current parameter.

  •  DMEN_Feeder_WireAmpacity The ampacity of the feeder as a current parameter.

  •  DMEN_Feeder_XPer1000ft The reactance per 1,000' for the feeder.

  •  DMEN_Feeder_ZPer1000ft The impedance per 1,000' for the feeder.

  •  DMEN_Feeder2_ConductorWireArea The area of the conductor wire of the second feeder as an area parameter. The area is for a single conductor wire. It does not account for parallel runs or the number of poles.

  •  DMEN_Feeder2_ConduitArea The area of the conduit of the second feeder as an area parameter.

  •  DMEN_Feeder2_ConduitFill The conduit fill of the second feeder as a percentage.

  •  DMEN_Feeder_EffectiveZPer1000ft The effective Z per 1,000' for the second feeder. Used to calculate voltage drop.

  •  DMEN_Feeder2_FrameSize The frame size of the upstream OCP of the second feeder for the distribution equipment as a current parameter.

  •  DMEN_Feeder2_GroundWireArea The area of the ground wire of the second feeder as an area parameter.

  •  DMEN_Feeder2_Length The length of the feeder of the second feeder as a length parameter.

  •  DMEN_Feeder2_NeutralWireArea The area of the neutral wire of the second feeder as an area parameter.

  •  DMEN_Feeder2_NeutralWireCount The number of neutral wires of the second feeder.

  •  DMEN_Feeder2_ParallelRuns The number of parallel runs of the second feeder.

  •  DMEN_Feeder2_RPer1000ft The resistance per 1,000' for the second feeder.

  •  DMEN_Feeder2_TripSize The trip size of the upstream OCP for the distribution equipment of the second feeder as a current parameter.

  •  DMEN_Feeder2_WireAmpacity The ampacity of the second feeder as a current parameter.

  •  DMEN_Feeder2_XPer1000ft The reactance per 1,000' for the second feeder.

  •  DMEN_Feeder2_ZPer1000ft The impedance per 1,000' for the second feeder.

Text Parameters​

  •  DMET_Feeder_ConductorWireArea The area of the conductor wire. The area is for a single conductor wire. It does not account for parallel runs or the number of poles.

    If there are two feeders, both conductor sizes are shown, separated by a slash.

  •  DMET_Feeder_ConductorWireSize The number of parallel runs and the size of the conductor wires. Displayed in the default fault current schedule.

    If there are two feeders, both feeder sizes are shown, separated by a slash.

  •  DMET_Feeder_ConductorWireSizeOnly The size of the conductor wires.

    If there are two feeders, both feeder sizes are shown, separated by a slash.

  •  DMET_Feeder_ConduitFill The conduit fill as a percentage.

    If there are two feeders, both conduit fills are shown, separated by a slash.

  •  DMET_Feeder_ConduitSize The size of the conduit.

    If there are two feeders, both conduit sizes are shown, separated by a slash.

  •  DMET_Feeder_EffectiveZPer1000ft The effective Z per 1,000' for the feeder. Used to calculate voltage drop.

    If there are two feeders, both values are shown, separated by a slash.

  •  DMET_Feeder_FeederID The feeder ID on the single-line diagram of the first feeder.

  •  DMET_Feeder_FrameSize The frame size of the upstream OCP of the first feeder for the distribution equipment.

  •  DMET_Feeder_GroundWireSize The size of the ground wire.

    If there are two feeders, both ground wire sizes are shown, separated by a slash.

  •  DMET_Feeder_IGConductor A Yes or No value that indicates whether the first feeder includes an IG conductor.

  •  DMET_Feeder_Length_ft The length of the feeder in feet. Displayed in the default fault current schedule.

    If there are two feeders, both lengths are shown, separated by a slash.

  •  DMET_Feeder_Length_m The length of the feeder in meters.

    If there are two feeders, both lengths are shown, separated by a slash.

  •  DMET_Feeder_NeutralWireSize The size of the neutral wire.

    If there are two feeders, both neutral wire sizes are shown, separated by a slash.

  •  DMET_Feeder_ParallelRuns The number of parallel runs of the first feeder.

  •  DMET_Feeder_RPer1000ft The resistance of the feeder per 1,000'.

    If there are two feeders, both resistances are shown, separated by a slash.

  •  DMET_Feeder_Trip_Poles The trip size and number of poles of the upstream OCP of the first feeder for the distribution equipment. The trip and poles are separated by a slash, for example, 100/3.

  •  DMET_Feeder_TripSize The trip size of the upstream OCP of the first feeder for the distribution equipment.

  •  DMET_Feeder_WireAmpacity The ampacity of the feeder wire of the first feeder.

  •  DMET_Feeder_WireCallout The callout of the first feeder. The callout lists the conduit size and all of the wire sizes, separated by a comma and a space.

  •  DMET_Feeder_WireCalloutCompact The callout of the first feeder. The callout lists the conduit size and all of the wire sizes, separated by a comma.

  •  DMET_Feeder_XPer1000ft The reactance of the feeder per 1,000'.

    If there are two feeders, both reactances are shown, separated by a slash.

  •  DMET_Feeder_ZPer1000ft The impedance of the feeder per 1,000'.

    If there are two feeders, both impedances are shown, separated by a slash.

  •  DMET_Feeder1_ConductorWireArea The area of the conductor wire of the first feeder. The area is for a single conductor wire. It does not account for parallel runs or the number of poles.

  •  DMET_Feeder1_ConductorWireSize The number of parallel runs and the size of the conductor wires of the first feeder.

  •  DMET_Feeder1_ConductorWireSizeOnly The size of the conductor wires of the first feeder.

  •  DMET_Feeder1_ConduitSize The size of the conduit of the first feeder.

  •  DMET_Feeder1_EffectiveZPer1000ft The effective Z per 1,000' of the first feeder. Used to calculate voltage drop.

  •  DMET_Feeder1_GroundWireSize The size of the ground wire of the first feeder.

  •  DMET_Feeder1_Length_ft The length in feet of the first feeder.

  •  DMET_Feeder1_Length_m The length in meters of the first feeder.

  •  DMET_Feeder1_NeutralWireSize The size of the neutral wire of the first feeder.

  •  DMET_Feeder1_RPer1000ft The resistance per 1,000' of the first feeder.

  •  DMET_Feeder1_XPer1000ft The reactance per 1,000' of the first feeder.

  •  DMET_Feeder1_ZPer1000ft The impedance per 1,000' of the first feeder.

  •  DMET_Feeder2_ConductorWireArea The area of the conductor wire of the second feeder. The area is for a single conductor wire. It does not account for parallel runs or the number of poles.

  •  DMET_Feeder2_ConductorWireSize The number of parallel runs and the size of the conductor wires of the second feeder.

  •  DMET_Feeder2_ConductorWireSizeOnly The size of the conductor wires of the second feeder.

  •  DMET_Feeder2_ConduitFill The conduit fill of the second feeder as a percentage.

  •  DMET_Feeder2_ConduitSize The size of the conduit of the second feeder.

  •  DMET_Feeder2_FeederID The feeder ID on the single-line diagram of the second feeder.

  •  DMET_Feeder2_FrameSize The frame size of the upstream OCP of the second feeder for the distribution equipment.

  •  DMET_Feeder2_EffectiveZPer1000ft The effective Z per 1,000' of the second feeder. Used to calculate voltage drop.

  •  DMET_Feeder2_GroundWireSize The size of the ground wire of the second feeder.

  •  DMET_Feeder2_IGConductor A Yes or No value that indicates whether the second feeder includes an IG conductor.

  •  DMET_Feeder2_Length_ft The length in feet of the second feeder.

  •  DMET_Feeder2_Length_m The length in meters of the second feeder.

  •  DMET_Feeder2_NeutralWireSize The size of the neutral wire of the second feeder.

  •  DMET_Feeder2_ParallelRuns The number of parallel runs of the second feeder.

  •  DMET_Feeder2_RPer1000ft The resistance per 1,000' of the second feeder.

  •  DMET_Feeder2_TripSize The trip size of the upstream OCP of the second feeder for the distribution equipment.

  •  DMET_Feeder2_WireAmpacity The ampacity of the second feeder.

  •  DMET_Feeder2_WireCallout The callout of the second feeder. The callout lists the conduit size and all of the wire sizes, separated by a comma and a space.

  •  DMET_Feeder2_WireCalloutCompact The callout of the second feeder. The callout lists the conduit size and all of the wire sizes, separated by a comma.

  •  DMET_Feeder2_XPer1000ft The reactance per 1,000' of the second feeder.

  •  DMET_Feeder2_ZPer1000ft The impedance per 1,000' of the second feeder.

Yes/No Parameters​

  •  DMEB_Feeder_NeutralDouble Whether the neutral wire of the first feeder is set to double the phase wire.

  •  DMEB_Feeder2_NeutralDouble Whether the neutral wire of the second feeder is set to double the phase wire.

Branch Circuit Device Shared Parameters​

The shared parameters added to branch circuit devices.

Numeric Parameters​

  •  DMEN_Fixture_Elevation The elevation of the device as a length parameter. Uses the Revit Elevation parameter if it exists. Otherwise uses the greatest Z value of the family geometry.

  •  DMEN_Equipment_FLA The FLA or BCSC of the fixture as a current parameter.

  •  DMEN_Equipment_MCA The MCA of the fixture as a current parameter.

  •  DMEN_Equipment_MOCP The MOCP of the fixture as a current parameter.

  •  DMEN_Feeder_ConductorWireArea The area of the conductor wire of the branch circuit connected to this device as an area parameter. The area is for a single conductor wire. It does not account for parallel runs or the number of poles.

  •  DMEN_Feeder_ConduitArea The area of the conduit of the branch circuit connected to this device as an area parameter.

  •  DMEN_Feeder_FrameSize The frame size of the branch circuit connected to this device as a current parameter.

  •  DMEN_Feeder_GroundWireArea The area of the ground wire of the branch circuit connected to this device as an area parameter.

  •  DMEN_Feeder_Length The length of the branch circuit connected to this device as a length parameter.

    If multiple devices are on the branch circuit, the average distance from the distribution equipment to the devices on the branch circuit will be displayed.

  •  DMEN_Feeder_NeutralWireArea The area of the neutral wire of the branch circuit connected to this device as an area parameter.

  •  DMEN_Feeder_ParallelRuns The number of parallel runs of the branch circuit connected to this device.

  •  DMEN_Feeder_TripSize The trip size of the branch circuit connected to this device as a current parameter.

  •  DMEN_VoltageDrop_Feeder The voltage drop on the branch circuit connected to this device.

Text Parameters​

  •  DMET_Feeder_ConductorWireSize The number of parallel runs and the size of the conductor wires of the branch circuit connected to this device.

  •  DMET_Feeder_ConductorWireSizeOnly The size of the conductor wires of the branch circuit connected to this device.

  •  DMET_Feeder_ConduitSize The size of the conduit of the branch circuit connected to this device.

  •  DMET_Feeder_FeederID The feeder ID on the single-line diagram of the branch circuit connected to this device.

  •  DMET_Feeder_FrameSize The frame size of the branch circuit connected to this device.

  •  DMET_Feeder_GroundWireSize The size of the ground wire of the branch circuit connected to this device.

  •  DMET_Feeder_Length_ft The length of the branch circuit connected to this device in feet.

    If multiple devices are on the branch circuit, the average distance from the distribution equipment to the devices on the branch circuit will be displayed.

  •  DMET_Feeder_Length_m The length of the branch circuit connected to this device in meters.

    If multiple devices are on the branch circuit, the average distance from the distribution equipment to the devices on the branch circuit will be displayed.

  •  DMET_Feeder_NeutralWireSize The size of the neutral wire of the branch circuit connected to this device.

  •  DMET_Feeder_ParallelRuns The number of parallel runs of the branch circuit connected to this device.

  •  DMET_Feeder_TripSize The trip size of the branch circuit connected to this device.

  •  DMET_Feeder_Trip_Poles The trip size and number of poles of the branch circuit connected to this device. The trip and poles are separated by a slash, for example, 100/3.

  •  DMET_Feeder_WireCallout The callout of the branch circuit connected to this device. The callout lists the conduit size and all of the wire sizes.

  •  DMET_Instance_CircuitDescription The circuit description of the branch circuit connected to this device.

  •  DMET_Instance_ThisDescription The circuit description of this device.

  •  DMET_VoltageDrop_Feeder The voltage drop on the branch circuit connected to this device.

Circuit Shared Parameters​

The shared parameters added to circuits.

Numeric Parameters​

  •  DMEN_Circuit_ConductorWireArea The area of the conductor wire as an area parameter. The area is for a single conductor wire. It does not account for parallel runs or the number of poles.

  •  DMEN_Circuit_ConduitArea The area of the conduit as an area parameter.

  •  DMEN_Circuit_ConduitFill The conduit fill as a percentage.

  •  DMEN_Circuit_FaultAtDevice The available fault current at the distribution equipment or branch circuit device connected to the circuit as a current parameter. Includes both the utility fault and motor contributions.

  •  DMEN_Circuit_FaultMotorDirectlyConnected The fault due to the branch circuit device, or due to motors directly connected to the distribution equipment connected to the circuit as a current parameter.

  •  DMEN_Circuit_FaultMotorTotal The total fault due to all motors in the system at the distribution equipment or branch circuit device connected to the circuit as a current parameter.

  •  DMEN_Circuit_FaultUtility The fault from the utility at the distribution equipment or branch circuit device connected to the circuit as a current parameter.

  •  DMEN_Circuit_GroundWireArea The area of the ground wire as an area parameter.

  •  DMEN_Circuit_Length The length of the circuit as a length parameter.

    If multiple devices are on the circuit, the average distance from the distribution equipment to the devices on the circuit will be displayed.

  •  DMEN_Circuit_NeutralWireArea The area of the neutral wire as an area parameter.

  •  DMEN_Circuit_ParallelRuns The number of parallel runs.

  •  DMEN_Circuit_Poles The number of poles.

  •  DMEN_Circuit_VoltageDrop The voltage drop of the circuit.

  •  DMEN_Circuit_VoltageDrop_Total The total voltage drop from the utility to the devices on the circuit.

Text Parameters​

  •  DMET_Circuit_ConductorWireSize The number of parallel runs and the size of the conductor wires.

  •  DMET_Circuit_ConductorWireSizeOnly The size of the conductor wires.

  •  DMET_Circuit_ConduitFill The conduit fill as a percentage.

  •  DMET_Circuit_ConduitSize The size of the conduit.

  •  DMET_Circuit_FaultAtDevice The available fault current at the distribution equipment or branch circuit device connected to the circuit. Includes both the utility fault and motor contributions.

    Displays a warning if the fault exceeds the AIC rating of the distribution equipment.

  •  DMET_Circuit_FaultAtDevice_NoWarnings The available fault current at the distribution equipment or branch circuit device connected to the circuit. Includes both the utility fault and motor contributions.

    Does not display a warning if the fault exceeds the AIC rating of the distribution equipment.

  •  DMET_Circuit_FaultMotorDirectlyConnected The fault due to the branch circuit device, or due to motors directly connected to the distribution equipment connected to the circuit.

  •  DMET_Circuit_FaultMotorTotal The total fault due to all motors in the system at the distribution equipment connected to the circuit.

  •  DMET_Circuit_FaultUtility The fault from the utility at the distribution equipment connected to the circuit.

  •  DMET_Circuit_FeederID The feeder ID used for the circuit on the single-line diagram.

  •  DMET_Circuit_GroundWireSize The size of the ground wire.

  •  DMET_Circuit_Length_ft The length of the circuit in feet.

    If multiple devices are on the circuit, the average distance from the distribution equipment to the devices on the circuit will be displayed.

  •  DMET_Circuit_Length_m The length of the circuit in meters.

    If multiple devices are on the circuit, the average distance from the distribution equipment to the devices on the circuit will be displayed.

  •  DMET_Circuit_NeutralWireSize The size of the neutral wire.

  •  DMET_Circuit_Number The circuit number.

  •  DMET_Circuit_ParallelRuns The number of parallel runs.

  •  DMET_Circuit_VoltageDrop The voltage drop of the circuit.

  •  DMET_Circuit_VoltageDrop_Total The total voltage drop from the utility to the devices on the circuit.

  •  DMET_Circuit_WireCallout The wire callout for the circuit using the calculated or specified wire size settings. Wire sizes are separated by a comma and a space.

  •  DMET_Circuit_WireCalloutCompact The wire callout for the circuit using the calculated or specified wire size settings. Wire sizes are separated by a comma.

  •  DMET_Circuit_WireCalloutHR The wire callout for the circuit using the calculated or specified wire size settings. Wire sizes are separated by a comma.

    Some callouts are hidden depending upon the Homerun wire callouts ▾ option set in the Project Options command.

Arc-Flash Shared Parameters​

The shared parameters added to distribution equipment related to arc-flash calculations.

Numeric Parameters​

  •  DMEN_ArcFlash_ArcingCurrentMaximum The maximum arcing current in amps.

  •  DMEN_ArcFlash_ArcingCurrentReduced The reduced arcing current in amps.

  •  DMEN_ArcFlash_ConductorGap The conductor gap in inches.

  •  DMEN_ArcFlash_EnclosureDepth The depth of the enclosure in inches.

  •  DMEN_ArcFlash_EnclosureHeight The height of the enclosure in inches.

  •  DMEN_ArcFlash_EnclosureWidth The width of the enclosure in inches.

  •  DMEN_ArcFlash_IncidentEnergyAtMaximumCurrent The incident energy at maximum arcing current in Joules/cm².

  •  DMEN_ArcFlash_IncidentEnergyAtReducedCurrent The incident energy at reduced arcing current in Joules/cm².

  •  DMEN_ArcFlash_MaximumIncidentEnergy The maximum arc-flash incident energy in Joules/cm².

  •  DMEN_ArcFlash_ProtectionBoundaryDistance The arc-flash-protection boundary distance as a length parameter.

  •  DMEN_ArcFlash_WorkingDistance The working distance as a length parameter.

Text Parameters​

  •  DMET_ArcFlash_ArcingCurrentMaximum The maximum arcing current in amps.

  •  DMET_ArcFlash_ArcingCurrentReduced The reduced arcing current in amps.

  •  DMET_ArcFlash_Calculate A Yes or No value that indicates whether the arc-flash is calculated for the distribution equipment. It also is used to indicate whether the distribution equipment should be displayed in the arc-flash schedule.

    The default arc-flash schedule includes this parameter as a hidden column. Any distribution equipment with the value set to No is not included in the schedule. Pieces of electrical equipment with their Part Type ▾ set to Equipment Switch are automatically set to No so they are not displayed in the schedule.

  •  DMET_ArcFlash_ConductorGap_inch The conductor gap in inches.

  •  DMET_ArcFlash_ConductorGap_mm The conductor gap in millimeters.

  •  DMET_ArcFlash_ElectrodeConfiguration The electrode configuration for the distribution equipment.

  •  DMET_ArcFlash_EnclosureDepth_inch The depth of the enclosure in inches.

  •  DMET_ArcFlash_EnclosureDepth_mm The depth of the enclosure in millimeters.

  •  DMET_ArcFlash_EnclosureHeight_inch The height of the enclosure in inches.

  •  DMET_ArcFlash_EnclosureHeight_mm The height of the enclosure in millimeters.

  •  DMET_ArcFlash_EnclosureWidth_inch The width of the enclosure in inches.

  •  DMET_ArcFlash_EnclosureWidth_mm The width of the enclosure in millimeters.

  •  DMET_ArcFlash_IncidentEnergyAtMaximumCurrent_cal The incident energy at maximum arcing current in calories/cm².

  •  DMET_ArcFlash_IncidentEnergyAtMaximumCurrent_J The incident energy at maximum arcing current in Joules/cm².

  •  DMET_ArcFlash_IncidentEnergyAtReducedCurrent_cal The incident energy at reduced arcing current in calories/cm².

  •  DMET_ArcFlash_IncidentEnergyAtReducedCurrent_J The incident energy at reduced arcing current in Joules/cm².

  •  DMET_ArcFlash_MaximumIncidentEnergy_cal The maximum arc-flash incident energy in calories/cm².

  •  DMET_ArcFlash_MaximumIncidentEnergy_J The maximum arc-flash incident energy in Joules/cm².

  •  DMET_ArcFlash_ProtectionBoundaryDistance_ft The arc-flash-protection boundary distance in feet.

  •  DMET_ArcFlash_ProtectionBoundaryDistance_mm The arc-flash-protection boundary distance in millimeters.

  •  DMET_ArcFlash_WorkingDistance_ft The working distance in feet.

  •  DMET_ArcFlash_WorkingDistance_mm The working distance in millimeters.

Fault Shared Parameters​

The shared parameters added to distribution equipment related to fault calculations.

Numeric Parameters​

  •  DMEN_Fault_FaultAtDevice The available fault current at the distribution equipment or branch circuit device as a current parameter. Includes both the utility fault and motor contributions.

  •  DMEN_Fault_FaultMotorDirectlyConnected The fault due to motors directly connected to the distribution equipment as a current parameter.

  •  DMEN_Fault_FaultMotorTotal The total fault due to all motors in the system as a current parameter.

  •  DMEN_Fault_FaultUtility The fault at the distribution equipment or branch circuit device from the utility as a current parameter.

  •  DMEN_Fault_FedFromFault The available fault current at the upstream distribution equipment as a current parameter.

  •  DMEN_Fault_FedFromFault1 The available fault current at the upstream distribution equipment connected to feeder 1 as a current parameter.

  •  DMEN_Fault_FedFromFault2 The available fault current at the upstream distribution equipment connected to feeder 2 as a current parameter.

  •  DMEN_Fault_Transformer_FaultAtPrimary The available fault at the primary of a transformer as a current parameter.

    Set to 0 if the distribution equipment is not a transformer.

Text Parameters​

  •  DMET_Fault_Display A Yes or No value that indicates whether the distribution equipment should be displayed in the fault current schedule.

    The default fault current schedule includes this parameter as a hidden column. Any distribution equipment with the value set to No is not included in the schedule. Pieces of electrical equipment with their Part Type ▾ set to Equipment Switch are automatically set to No so they are not displayed in the schedule.

  •  DMET_Fault_FaultAtDevice The available fault current at the distribution equipment or branch circuit device. Includes both the utility fault and motor contributions.

    Displays a warning if the fault exceeds the AIC rating of the distribution equipment.

  •  DMET_Fault_FaultAtDevice_NoWarnings The available fault current at the distribution equipment or branch circuit device. Includes both the utility fault and motor contributions.

    Does not display a warning if the fault exceeds the AIC rating of the distribution equipment.

  •  DMET_Fault_FaultMotorDirectlyConnected The fault due to motors directly connected to the distribution equipment.

  •  DMET_Fault_FaultMotorTotal The total fault due to all motors in the system.

  •  DMET_Fault_FaultUtility The fault at the distribution equipment or branch circuit device from the utility.

  •  DMET_Fault_FedFromFault The available fault current at the upstream distribution equipment.

  •  DMET_Fault_Transformer_FaultAtPrimary The available fault at the primary of a transformer.

    Blank if the distribution equipment is not a transformer.

Voltage Drop Shared Parameters​

The shared parameters added to distribution equipment related to voltage drop calculations.

Numeric Parameters​

  •  DMEN_VoltageDrop_Feeder The cumulative voltage drop on the feeder to the distribution equipment.

    If the distribution equipment has two feeders, this value is the largest of the two voltage drops.

  •  DMEN_VoltageDrop_Feeder1 The voltage drop on feeder 1 to the distribution equipment.

  •  DMEN_VoltageDrop_Feeder2 The voltage drop on feeder 2 to the distribution equipment.

  •  DMEN_VoltageDrop_MaxCircuit The largest voltage drop on all of the branch circuits on the distribution equipment.

  •  DMEN_VoltageDrop_MaxCircuit_Length The length of the branch circuit with the largest voltage drop as a length parameter.

  •  DMEN_VoltageDrop_Total The total voltage drop from the utility to the branch circuit devices. It is calculated as the sum of the largest branch circuit voltage drop and the larger of the two feeder voltage drops.

  •  DMEN_VoltageDrop_Transformer The voltage drop through the transformer if the distribution equipment is a transformer.

Text Parameters​

  •  DMET_VoltageDrop_Display A Yes or No value that indicates whether the distribution equipment should be displayed in the voltage drop schedule.

    The default voltage drop schedule includes this parameter as a hidden column. Any distribution equipment with the value set to No is not included in the schedule. Pieces of electrical equipment with their Part Type ▾ set to Equipment Switch are automatically set to No so they are not displayed in the schedule.

  •  DMET_VoltageDrop_Feeder The cumulative voltage drop on the feeder to the distribution equipment.

    If the distribution equipment has two feeders, this value is the largest of the two voltage drops.

    Displays a warning if this value exceeds 2% or 3%, depending upon the Feeder voltage drop percentage limit option in the Project Options command.

  •  DMET_VoltageDrop_Feeder_NoWarnings The cumulative voltage drop on the feeder to the distribution equipment.

    If the distribution equipment has two feeders, this value is the largest of the two voltage drops.

    Does not display a warning if this value exceeds a certain percentage.

  •  DMET_VoltageDrop_Feeder1 The non-cumulative voltage drop on feeder 1 to the distribution equipment.

  •  DMET_VoltageDrop_Feeder2 The non-cumulative voltage drop on feeder 2 to the distribution equipment.

  •  DMET_VoltageDrop_MaxCircuit The largest voltage drop on all of the branch circuits on the distribution equipment.

    Displays a warning if this value exceeds 3%.

  •  DMET_VoltageDrop_MaxCircuit_ConductorWireSize The number of parallel runs and the size of the conductor wires of the branch circuit with the largest voltage drop.

  •  DMET_VoltageDrop_MaxCircuit_ConductorWireSizeOnly The size of the conductor wires of the branch circuit with the largest voltage drop.

  •  DMET_VoltageDrop_MaxCircuit_Length_ft The length of the branch circuit with the largest voltage drop in feet.

  •  DMET_VoltageDrop_MaxCircuit_Length_m The length of the branch circuit with the largest voltage drop in meters.

  •  DMET_VoltageDrop_MaxCircuit_NoWarnings The largest voltage drop on all of the branch circuits on the distribution equipment.

    Does not display a warning if this value exceeds 3%.

  •  DMET_VoltageDrop_MaxCircuit_Number The circuit number of the branch circuit with the largest voltage drop.

  •  DMET_VoltageDrop_MaxCircuit_WireCallout The callout of the branch circuit with the largest voltage drop. The callout lists the conduit size and all of the wire sizes, separated by a comma and space.

  •  DMET_VoltageDrop_MaxCircuit_WireCalloutCompact The callout of the branch circuit with the largest voltage drop. The callout lists the conduit size and all of the wire sizes, separated by a comma.

  •  DMET_VoltageDrop_Total The total voltage drop from the utility to the branch circuit devices. It is calculated as the sum of the largest branch circuit voltage drop and the larger of the two feeder voltage drops.

    Displays a warning if this value exceeds 5%.

  •  DMET_VoltageDrop_Total_NoWarnings The total voltage drop from the utility to the branch circuit devices. It is calculated as the sum of the largest branch circuit voltage drop and the larger of the two feeder voltage drops.

    Does not display a warning if this value exceeds 5%.

  •  DMET_VoltageDrop_Transformer The voltage drop through the transformer if the distribution equipment is a transformer.

Selective Coordination Shared Parameters​

The shared parameters added to distribution equipment, branch circuit devices, and circuits related to breaker curves and selective coordination.

  •  DMET_MainOCP_Setting_Description The manufacturer and model of the main disconnect for the distribution equipment.

  •  DMET_MainOCP_Setting_I2T The I²T setting of the main disconnect for the distribution equipment.

  •  DMET_MainOCP_Setting_InstPickup The instantaneous pickup setting of the main disconnect for the distribution equipment.

  •  DMET_MainOCP_Setting_LTDelay The long-time delay setting of the main disconnect for the distribution equipment.

  •  DMET_MainOCP_Setting_STDelay The short-time delay setting of the main disconnect for the distribution equipment.

  •  DMET_MainOCP_Setting_STPickup The short-time pickup setting of the main disconnect for the distribution equipment.

  •  DMET_OCP_Setting_Description The manufacturer and model of the overcurrent protection for the device or circuit.

  •  DMET_OCP_Setting_I2T The I²T setting of the overcurrent protection for the device or circuit.

  •  DMET_OCP_Setting_InstPickup The instantaneous pickup setting of the overcurrent protection for the device or circuit.

  •  DMET_OCP_Setting_LTDelay The long-time delay setting of the overcurrent protection for the device or circuit.

  •  DMET_OCP_Setting_STDelay The short-time delay setting of the overcurrent protection for the device or circuit.

  •  DMET_OCP_Setting_STPickup The short-time pickup setting of the overcurrent protection for the device or circuit.

  •  DMET_OCP2_Setting_Description The manufacturer and model of the overcurrent protection for the second feeder of the distribution equipment.

  •  DMET_OCP2_Setting_I2T The I²T setting of the overcurrent protection for the second feeder of the distribution equipment.

  •  DMET_OCP2_Setting_InstPickup The instantaneous pickup setting of the overcurrent protection for the second feeder of the distribution equipment.

  •  DMET_OCP2_Setting_LTDelay The long-time delay setting of the overcurrent protection for the second feeder of the distribution equipment.

  •  DMET_OCP2_Setting_STDelay The short-time delay setting of the overcurrent protection for the second feeder of the distribution equipment.

  •  DMET_OCP2_Setting_STPickup The short-time pickup setting of the overcurrent protection for the second feeder of the distribution equipment.