Free Trial Download and try today

High Ventilation Loads in a Zone

Posted on November 10th, 2011. Last updated on June 14th, 2023.

Q: Why is the ventilation load calculation in one of my zones so high?

A: Very high ventilation values can occur when the required ventilation for a room exceeds the minimum required supply air, which will cause some load calculation methods to fail.

Solution

First, follow these steps to confirm that the problem is being caused by ventilation exceeding supply in a room and not something else:

  1. Run the Print Load Calculations command.
  2. Check the box next to Print Ventilation Schedule and select the zone from the list.
  3. Press the Calculate and Print Loads button.
  4. In the ventilation schedule for the zone, find the critical room, highlighted in bold. Load calculations for the zone are most heavily influenced by the critical room.

If the Discharge Outdoor Air Fraction for the critical room is less than 1, the high ventilation load is caused by something else.

If the Discharge Outdoor Air Fraction for the critical room is 1, you need to set a maximum ventilation-to-supply ratio for the project using these steps:

  1. Run the Project Info command.
  2. Check the box next to Maximum Room Ventilation Percentage, then enter a value less than 1 in the field provided (e.g., 0.25 for 25% outside air).
  3. Press the OK button to save your changes and close the dialog box.

When you recalculate the loads, the ventilation load should be significantly lower.

Cause

For rooms that require little conditioned air, the minimum required ventilation from outside air can exceed the minimum required supply air, resulting in a ventilation-to-supply percentage of 100% (or higher). The ventilation calculations used by  ASHRAE 62.1 and the International Mechanical Code are not designed to handle that percentage, resulting in a zone that “needs” unrealistically high ventilation.

Setting a Maximum Room Ventilation Percentage will cause the software to increase the supply air to maintain the specified ventilation-to-supply percentage.

Related Articles

Filter by
Post Page
HVAC Load Calculations Electrical
Sort by

Ventilation Calculations

Design Master HVAC offers two methods for calculating the ventilation air required in a zone: minimum, and ASHRAE 62.1.

24

Correctly Using ASHRAE 62.1 or IMC Ventilation Calculations

When calculating ventilation rates, make sure you set the calculation method in Project Info as well as set the ventilation rates for rooms types according to the code being used.

24

Ventilation or Psychrometric Airflow Values are 0

If your building load calculations don’t show any outside air, ventilation load, or airflow, you must modify your project information or insert supply diffusers with airflow on your drawing.

24

No Outside Air in Building Load Calculations

If your building load calculations don’t show any outside air, ventilation load, or airflow, you must modify your project information or insert supply diffusers with airflow on your drawing.

14

Room Loads vs. System Loads

The room load only accounts for air supplied to the room, while the system load accounts for the total load of the air handler, including ventilation and plenum loads.

14

Exporting Load Calculations (and Other HTML Outputs) to Excel

Some HVAC and Electrical reports can be exported as HTML files. Here are three easy ways to open those files in Excel.

0