You are here: Home > Support > Blog > Feeder and Service Load Calculations

Feeder and Service Load Calculations

Thursday, March 13th, 2014

Design Master Electrical can calculate feeder and service loads based upon NEC 220 Section III and Section IV. This page lists each code reference and how to properly set up your model for that calculation. This page is intended to be used as a reference together with the NEC. It assumes that you know which section in the NEC that you need to comply with. You can then look up the appropriate section below and see how to model it.

III. Feeder and Service Load Calculations

220.42 General Lighting. To use the demand factors for general lighting in Table 240.42, you must be using the general lighting calculations. Otherwise, all lighting has a calculated load of 125%. In the Panel dialog box, press the Feeder and Service Calculation Settings button. Set the occupancy area associated with the panel in the Occupancy Areas section. Set the areas on the panels furthest from the utility as possible. The areas will be carried up the one-line and added to upstream panels. The area on a panel is the areas specified in the Occupancy Areas section, plus the sum of the areas of the panels connected to it.

Dwelling units: Use the 3 VA / sf Occupancy Areas, NEC Table 220.42 Demand Area field to set the area.

Hospitals: Use the 2 VA / sf Occupancy Areas, NEC Table 220.42 Demand Area field to set the area. For areas where the note on Table 220.42 apply (where the entire lighting is likely to be used at one time), use the 100% Demand Area field.

Hotels and motels: Use the 2 VA / sf Occupancy Areas, NEC Table 220.42 Demand Area field to set the area. For areas where the note on Table 220.42 apply (where the entire lighting is likely to be used at one time), use the 100% Demand Area field.

Warehouses: Use the 0.25 VA / sf Occupancy Areas, NEC Table 220.42 Demand Area field to set the area.

All others: Use the NEC Table 220.42 Demand Area field for the appropriate power density to set the area. See Table 220.12 for a list of occupancies.

220.43 Show-Window and Track Lighting. Either create a fixture to represent the load or use fixed loads.

Create a Fixture: Create a fixture in the light fixture schedule to represent the load. For show windows, each fixture will represent 1 linear foot of show window. Set the load to 0.2 kVA. For track lighting, each fixture will represent 2 feet of track. Set the load to 0.15 kVA. Insert fixtures on the drawing to represent the appropriate length of show window or track. Circuit the fixtures normally.

Fixed Loads: Use the Circuiting dialog box to specify fixed loads on circuits with show-window or track lighting. Draft the lighting either by inserting light fixtures that you do no circuit or have 0 load, or use standard AutoCAD drafting commands to insert light fixtures that are not connected to the Design Master Electrical database.

220.44 Receptacle Loads — Other Than Dwelling Units. Use the General: Receptacle load type for receptacles that should be calculated based upon this section. Typically, the load for each receptacle will be 0.18 kVA. The load on the panel will be based upon Table 220.44.

220.50 Motors. See the Motor Load Calculations page for a description of how to use the Single Motor and Multiple Motor fields to specify motors.

220.41 Fixed Electrical Space Heating. Use the General: Heating load type for devices that should be calculated based upon this section.

220.52 Small-Appliance and Laundry Loads — Dwelling Unit.

(A) Small-Appliance Circuit Load. Use the Dwelling Unit: Small Appliance load type for devices that are on a small-appliance circuit. The specific load on the device does not matter. If any devices with this load type are on a circuit, the load on the circuit will be 1.5 kVA. The Load Calculation Method for the panel must be set to Dwelling Unit, Section III to use this code section.

(B) Laundry Circuit Load. Use the Dwelling Unit: Laundry load type for devices on a laundry circuit. The load on the circuit will be at least 1.5 kVA. If the load on the devices is greater than 1.5 kVA, the actual device load is used. The Load Calculation Method for the panel must be set to Dwelling Unit, Section III to use this code section.

220.53 Appliance Load — Dwelling Unit(s). Use the Dwelling Unit: Appliance load type for devices that are appliances. If the appliance is also a motor, use the Dwelling Unit: Appliance Motor load type. Use the Demand Factor field to specify the number of appliances the load represents. The Load Calculation Method for the panel must be set to Dwelling Unit, Section III to use this code section.

220.54 Electrical Clothes Dryers — Dwelling Unit(s). Use the Dwelling Unit: Electric Dryer load type for electric dryers. You are responsible for specifying a value of at least 5 kVA for the load on the dryer. Use the Demand Factor field to specify the number of appliances the load represents. The Load Calculation Method for the panel must be set to Dwelling Unit, Section III to use this code section.

220.55 Electrical Ranges and Other Cooking Appliances — Dwelling Unit(s). Use the Dwelling Unit: Electric Cooking load type for electric ranges, wall-mounted ovens, counter-mounted cooking units, and other household cooking appliances. Use the Demand Factor field to specify the number of appliances the load represents.

220.56 Kitchen Equipment — Other Than Dwelling Unit(s). Use the General: Kitchen load type for commercial kitchen equipment. Use the Demand Factor field to specify the number of appliances the load represents.

220.60 Noncoincident Loads. When both noncoincident loads are connected to the same panel, use the General: Diversified load type for the smaller of the two loads. Set the Demand Factor field to 0. For heating and cooling loads, use the Heating and Cooling load types. The larger of the heating or cooling load will be used for the feeder load total. There is no way to model noncoincident loads connected to separate panels. If you specify the load normally, panels that have both loads on them will have feeder load totals that are too high. If you specify the load using the Diversified load type, the panel with the diversified device on it will have a feeder load total that is too low.

IV. Option Feeder and Service Load Calculations

220.82 Dwelling Unit. In the Panel dialog box, press the Feeder and Service Calculation Settings button. Set the Load Calculation Method to Dwelling Unit, Section IV to calculate the feeder load total using this section.

(A) Feeder and Service Load. You are responsible for specifying a 100A feeder.

(B) General Loads.

(1) Use the 3 VA / sf Occupancy Areas, NEC Table 220.42 Demand Area field to set the area.

(2) Use the Dwelling Unit: Small Appliance and Dwelling Unit: Laundry load types for devices on these circuits.

(3) Use the Dwelling Unit: Appliance load type for a, c, and d. Use the Dwelling Unit: Electric Cooking load type for b.

(4) Use the Dwelling Unit: Appliance Motor load type for these motors.

(C) Heating and Air-Conditioning Load.

(1) Use the Dwelling Unit: Cooling, Largest Motor, Dwelling Unit: Cooling, Single Motor, and Dwelling Unit: Heat and Cooling Motor load types for this load.

(2) Use the Dwelling Unit:Heat and Cooling Motor load type for the heat pump load.

(3) Use the Dwelling Unit: Heat and Cooling Motor load type for the heat pump compressor. Use the Dwelling Unit: Heating load type for supplemental heating.

(4) Use the Dwelling Unit: Heating load type for the electric space heaters. Use the Demand Factor to specify the number of heaters the load represents.

(5) Use the Dwelling Unit: Heating load type for the electric space heaters. Use the Demand Factor to specify the number of heaters the load represents.

(6) Use the General: Heating load type for continuous heating. Do not use any of the Dwelling Unit heating or cooling load types if you need to use this code section.

220.83 Existing Dwelling Unit. In the Panel dialog box, press the Feeder and Service Calculation Settings button. Set the Load Calculation Method to Dwelling Unit, Existing to calculate the feeder load total using this section.

(A) Where Additional Air-Conditioning Equipment or Electric Space-Heating Equipment Is Not to Be Installed.

(1) Use the 3 VA / sf Occupancy Areas, NEC Table 220.42 Demand Area field to set the area.

(2) Use the Dwelling Unit: Small Appliance and Dwelling Unit: Laundry load types for devices on these circuits.

(3) Use the Dwelling Unit: Appliance load type for a, c, and d. Use the Dwelling Unit: Electric Cooking load type for b.

(B) Where Additional Air-Conditioning Equipment or Electric Space-Heating Equipment Is to Be Installed. Use the Dwelling Unit: Cooling, Largest Motor and Dwelling Unit: Cooling, Single Motor load types for air-conditioning equipment. Use the Dwelling Unit: Heating load type for central electric space heating and separately controlled space-heating units.

(1) Use the 3 VA / sf Occupancy Areas, NEC Table 220.42 Demand Area field to set the area.

(2) Use the Dwelling Unit: Small Appliance and Dwelling Unit: Laundry load types for devices on these circuits.

(3) Use the Dwelling Unit: Appliance load type for a, c, and d. Use the Dwelling Unit: Electric Cooking load type for b.

220.84 Multifamily Dwelling. In the Panel dialog box, press the Feeder and Service Calculation Settings button. Set the Load Calculation Method to Dwelling Unit, Section IV to calculate the feeder load total using this section.

(A) Feeder or Service Load. This calculation method is for three or more dwelling units. You have to use a different calculation method for a single dwelling unit. The Load Calculation Method selection includes a choice for the calculation that will be used for a single dwelling unit. This calculation method also requires 8 kVA of electric cooking load if there is no electric cooking. You have to manually specify that load on the panel.

(B) House Loads. Enter house loads using the various General load types.

(C) Connected Loads.

(1) Use the 3 VA / sf Occupancy Areas, NEC Table 220.42 Demand Area field to set the area.

(2) Use the Dwelling Unit: Small Appliance and Dwelling Unit: Laundry load types for devices on these circuits.

(3) Use the Dwelling Unit: Appliance load type for a, c, and d. Use the Dwelling Unit: Electric Cooking load type for b.

(4) Use the Dwelling Unit: Appliance Motor load type for these motors.

(5) Use the Dwelling Unit: Heating, Dwelling Unit: Cooling, Largest Motor, Dwelling Unit: Other Motors, and Dwelling Unit: Heating and Cooling Motor load types for the air-conditioning and electric space-heating loads.

220.85 Two Dwelling Units. If two dwelling units are calculated using this method, it is assumed that they are identical. The total load for both dwelling units is multiplied by 1.5 to increase it from 2 to 3 units, then a demand factor of 45% is applied.

220.86 Schools. Set the Load Calculation Method to School to use this code section.

2208.87 Determining Existing Loads. Use the Metered Demand field in the panel to specify the existing load.

220.88 New Restaurants. Set the Load Calculation Method to Restaurant, All Electric or Restaurant, Not All Electric to use this code section.

V. Farm Load Calculations. Farm load calculations are not included in Design Master Electrical.

Article 550 — Mobile Homes, Manufactured Homes, and Mobile Home Parks

550.31 Allowable Demand Factors. Set the Load Calculation Method to Mobile Home Park to use this code section.

Set the number of mobile homes for table 550.31 using the Mobile Homes field.

Use the Marina / Mobile Home / RV load type for the load on each mobile home lot.

Article 551 — Recreation Vehicles and Recreational Vehicle Parks.

551.73 Calculated Load. Set the Load Calculation Method to RV Park to use this code section.

Set the number of recreational vehicle sites using the Recreational Vehicle Sites field.

Use the Marina / Mobile Home / RV load type for the load on each recreational vehicle site.

Article 555 — Marinas and Boatyards

555.12 Load Calculations for Service and Feeder Conductors. Set the Load Calculation Method to Marina or Marina with Sub-Meters to use this code section.

Set the number of receptacles for table 555.12 using the Shore Power Receptacles field.

Use the Marina / Mobile Home / RV load type for the load on the shore power receptacles. If multiple shore power receptacles are provided for an individual boat slip, set the Demand Factor to 1 for the largest receptacle load and set it to 0 for all the others.

Leave a Reply

Products

Electrical for Revit

Electrical for AutoCAD

HVAC for AutoCAD

Photometrics for AutoCAD

Support

Contact Support

Install & Update Instructions

Weekly Training

Support Articles

User Manuals

Tutorials

Discussion Forum

Release Notes

Downloads

Wish List

Remote Support

Company

About

Awards

Newsletter

Blog

Customer Stories

Pricing

Electrical for Revit

Electrical for AutoCAD

HVAC for AutoCAD

Photometrics for AutoCAD

Free Trial

Electrical for Revit

Electrical for AutoCAD

HVAC for AutoCAD

Photometrics for AutoCAD

©2001-2017, Design Master Software, Inc