Electrode Configurations for Arc-Flash Calculations

Tuesday, March 26th, 2019

In order to calculate arc-flash for a piece of distribution equipment, you must set its electrode configuration as described in IEEE Std 1584-2018 Table 9.

This article illustrates each electrode configuration so you can determine the appropriate option for your distribution equipment.

VCB

This image shows an example of a Vertical conductors or electrodes inside a metal box or enclosure configuration.

The conductors extend downward from the top of a metal box or enclosure.

This configuration typically results in lower incident energy values than other configurations except for VOA.

VCBB

This image shows an example of a Vertical conductors or electrodes terminated in an insulating barrier inside a metal box or enclosure configuration.

The conductors extend downward from the top of a metal box or enclosure and terminate in an insulating barrier.

This configuration typically results in higher incident energy values than other configurations except for HCB.

HCB

This image shows an example of a Horizontal conductors or electrodes inside a metal box or enclosure configuration.

The conductors extend outward from the back of a metal box or enclosure.

This configuration typically results in the highest incident energy values.

VOA

This image shows an example of a Vertical conductors or electrodes in open air configuration.

The conductors extend downward and are not enclosed.

This configuration typically results in the lowest incident energy values.

HOA

This image shows an example of a Horizontal conductors or electrodes in open air configuration.

The conductors extend outward and are not enclosed.

This configuration typically results in higher incident energy values than VOA and VCB, but lower than VCBB and HCB.

Related Articles

Filter by
Post Page
Electrical Electrical RT Calculations Training Recording Electrical RT Training Electrical Training Light Fixtures Electrical Rooms
Sort by

How Building Angle Affects Calculations

The “Building Angle” setting offsets the axes along which wire length calculations are performed, which can greatly impact several figures in your project.

24

Training Recording: Branch Circuit Fault Calculations

This training video shows you how fault is calculated for branch circuits in Design Master Electrical RT 2.0.

18

Dwelling Unit Load Calculations

This training video teaches you how to calculate feeder and service loads for dwelling units in Design Master Electrical.

18

Base Units and Photometrics Calculations

If your photometrics calculations appear too condensed or spread out, you may have your base units set incorrectly.

16

Room Data and Photometrics Show Different Foot-candle Values

Different values for room and point-by-point foot-candle calculations are a result of different calculation methods.

14

Arc-Flash Overview

You can use Design Master Electrical to calculate arc-flash, display the calculations on the drawing, and print stickers to place on distribution equipment.

14

Products

Electrical for Revit

Electrical for AutoCAD

HVAC for AutoCAD

Photometrics for AutoCAD

System Requirements

Support

Contact Support

Install & Update Instructions

Online Training

Knowledge Base

User Manuals

Tutorials

Release Notes

Downloads

Wish List

Remote Support

Company

About

Customer Stories

Awards

Newsletter

Blog

Pricing

Electrical for Revit

Electrical for AutoCAD

HVAC for AutoCAD

Photometrics for AutoCAD

Free Trial

Electrical for Revit

Electrical for AutoCAD

HVAC for AutoCAD

Photometrics for AutoCAD

866-516-9497
19401 40th Ave W, Suite 302
Lynnwood, WA 98036
support@designmaster.biz

©2001-2021, Design Master Software, Inc