Room Data and Photometrics Show Different Foot-candle Values

Tuesday, April 30th, 2019

Q: I have a room defined on my drawing that shows a value for Foot-candles Actual. I’ve also calculated the average foot-candles for the room at workspace height using point-by-point photometrics, which shows a different value. Why are these values different?

A: The foot-candle calculation for rooms is less precise than the calculation for point-by-point photometrics.

The room calculation uses the zonal cavity method, which is an older formula used before computers were powerful and available enough to perform more sophisticated calculations. Only the size of the room and the total lumens produced by a single type of light fixture are taken into account; multiple light fixture types are not accounted for. The calculation does not account for light fixture placement within the room; it assumes you have a competent lighting design. The calculation also does not make full use of IES files. For more information about how this calculation is used in the software, see the Edit Room Label List page of the user manual.

Point-by-point calculations account for the size of the room, the placement and properties of each light fixture, all information included in IES files, and more; the result is a much more accurate and precise calculation.

Typically, the foot-candle calculation for rooms should only be relied on for general estimations. If you are using multiple light fixture types, are not sure about the quality of your lighting design, have IES files for your fixtures, or just want to be sure you’re getting accurate figures, use point-by-point photometrics.

Related Articles

Filter by
Post Page
Electrical Electrical RT Calculations Electrical RT General Electrical Customization Distribution Equipment (Panels and Transformers) Light Fixtures Electrical Rooms
Sort by

Arc-Flash Settings and Sensitivity (IEEE Std 1584-2018)

There are several factors that can influence arc-flash calculations, such as the working distance and the electrode configuration.

8

How to Use or Create a Custom Equipment Callout

You can customize the information displayed in equipment callouts, along with how custom equipment callouts look.

8

Electrode Configurations for Arc-Flash Calculations

This article will help you determine the electrode configuration for your distribution equipment, in order to perform arc-flash calculations.

8

Voltage Drop and Transformers Options

There are three options available for calculating voltage drop at transformers, depending on how your transformers are configured.

8

Arc-Flash Settings and Sensitivity (IEEE Std 1584-2002)

There are several factors that can influence arc-flash calculations, such as the working distance and whether the distribution equipment is enclosed.

8

COMcheck Lighting Export

You can use the Export to COMcheck command to export some lighting information in Design Master Electrical to a COMcheck file.

8

Products

Electrical for Revit

Electrical for AutoCAD

HVAC for AutoCAD

Photometrics for AutoCAD

Support

Contact Support

Install & Update Instructions

Online Training

Knowledge Base

User Manuals

Tutorials

Release Notes

Downloads

Wish List

Remote Support

Company

About

Customer Stories

Awards

Newsletter

Blog

Pricing

Electrical for Revit

Electrical for AutoCAD

HVAC for AutoCAD

Photometrics for AutoCAD

Free Trial

Electrical for Revit

Electrical for AutoCAD

HVAC for AutoCAD

Photometrics for AutoCAD

©2001-2019, Design Master Software, Inc