NEC 220.55 for Single-Phase Ranges and Three-Phase Service

Posted on December 26th, 2019. Last updated on December 26th, 2019.

Q: My project has single-phase ranges supplied by a three-phase panel. My manual load calculation for the ranges based upon NEC 220.55 doesn’t match Design Master’s calculation. How is the load being calculated?

A: This calculation has several moving parts, including one that is not explicitly mentioned in NEC 220.55 itself but is shown in Annex D, Example D5(a). This article will provide another example with some additional context. Relevant information about the project is as follows:

 

# of Ranges, Phase A-B 28
# of Ranges, Phase B-C 20
# of Ranges, Phase C-A 24
Connected Load per Range 9.1 kVA

To calculate the load:

  1. Find the maximum number of ranges between any two phases.
    In this example, phase A-B has the most ranges at 28.
  2. Multiply that number by 2.
    28 ranges * 2 = 56 ranges
  3. Using that number, calculate the demand based upon NEC Table 220.55.
    This example will use Column C (rating between 8.75 and 12 kVA). For 56 ranges, the demand is 25 kVA plus 0.75 kVA for each range.
    25 kVA + (0.75 kVA * 56 ranges) = 67 kVA
  4. Divide that number by 2 to calculate the single-phase load.
    67 kVA / 2 = 33.5 kVA
  5. Multiply that number by 3 to calculate the three-phase load.
    33.5 kVA * 3 = 100.5 kVA

The panel schedule footer will display the connected load and number of ranges for each phase, as well as the calculated load, rounded to the nearest integer (in this case, 101 kVA):

Related Articles

Filter by
Post Page
Electrical Training Recording Electrical Training Distribution Equipment (Panels and Transformers) Electrical Customization Circuiting ElectroBIM ElectroBIM General One-Line Diagrams Light Fixtures Calculations Electrical Drafting Electrical General
Sort by

Panel Schedule Customization Example

This video provides an example of how to customize a panel schedule in Design Master Electrical.

8

The Circuiting Command

This training video teaches you how to use the Circuiting command in Design Master Electrical.

8

Solar/Photovoltaic Systems in Design Master Electrical

Design Master can’t perform calculations for DC systems like solar arrays, but you can model them as generators to connect the AC side to your system.

0

Ground Wire Is Too Large

If you upsize your conductors, Design Master will automatically upsize your ground in accordance with NEC 250.122(B).

0

Training Recording: New Electrical 8.7 Features

This training video shows you the new features introduced and improvements made in Design Master Electrical 8.7.

0

Circuiting and Homeruns with Junction Boxes

You cannot circuit the junction box device type, but you can model a different device type after a junction box and circuit that.

0